What are the separation distance requirements for underground piping?
The separation distance for potable water and sewer pipelines located in the public right-of-way is governed by Arizona Administrative Code (AAC) R-18-5-502.C. The separation distance for reclaimed water pipelines located in the public right-of-way is governed by AAC R-18-9-602.F. The Maricopa Association of Government’s "Uniform Standard Details for Public Works Construction" standards 404-1 and 404-2 detail the separation distance and protection requirements for the installation of potable water, reclaimed water and sewer pipelines for MAG participants.

The separation distance between potable water and sewer pipelines from other pipelines such as non-potable ground, surface, irrigation, storm, industrial, etc., pipelines located in the public right-of-way is not defined by the regulations or MAG standards. The MCESD recommends that these non-potable pipelines:
- Be separated from potable water pipelines as specified by AAC R-18-5-502.C.
- Be located no closer than two feet vertically nor six feet horizontally from all other pipelines unless the non-potable pipeline is encased in at least six inches of concrete or using mechanical joint ductile iron pipe or other materials of equivalent or greater tensile and compressive strength at least 10 feet beyond any point on the pipeline conveyance within the specified minimum separation distance.

The MCESD will determine the separation distance requirements for these pipelines and pipelines not located in the public right-of-way on a case-by-case basis. For more information, download the Uniform Standard Details for Public Works Construction (PDF).

Show All Answers

1. What standards and references are used for the review and approval of engineering designs?
2. What treatment processes have been utilized on previously approved projects?
3. What information is required for a blending plan approval?
4. What are the separation distance requirements for underground piping?
5. What are the design requirements for hose bibbs and hose stations?